Certified F-Gas Services

Complete fluorinated refrigerant management in compliance with Regulation (EU) 2024/573

‎ ‎ ‎ ‎

Equipment containing fluorinated refrigerants must be installed, maintained and serviced in full compliance with Regulation (EU) 2024/573 and its implementing provisions.

Il Disgelo provides a complete F-Gas service for climatic chambers, temperature test chambers and environmental simulation systems, ensuring compliant operations, up-to-date documentation and full traceability of all activities performed.


What Is GWP?

GWP (Global Warming Potential) measures how much a gas contributes to global warming compared with CO₂, which has a GWP of 1. A refrigerant with a GWP of 1,400 released into the atmosphere has the same effect as 1,400 kg of CO₂ for every kg of gas. The F-Gas Regulation specifically restricts refrigerants with a high GWP.

RefrigerantGWPUse in climatic chambers
R744 (CO₂)1Natural refrigerant circuits, down to about −50 °C
R472A353Ultra-low temperatures, alternative to R23
R472B526Ultra-low temperatures, alternative to R23
R449A1,397Single-stage circuits or high stage of cascade systems
R404A3,922Older systems
R2314,800Traditional cascade systems down to −70 °C and below


F-Gas Regulation: Key Deadlines

DateWhat changesWho is affected
11 March 2024Regulation (EU) 2024/573 enters into forceEveryone
1 January 2025Ban on placing on the market new self-contained chambers using refrigerants with GWP ≥ 150, unless required by site safety requirementsNew chambers
1 January 2025Ban on using virgin HFCs with GWP ≥ 2,500 for servicing (e.g. R404A)Existing chambers
31 December 2028End of the derogation for chambers operating below −50 °C (Implementing Regulation 2024/2729)New ultra-low temperature chambers
1 January 2030Reclaimed or recycled gases with GWP ≥ 2,500 are no longer allowed for servicingExisting chambers
1 January 2032Ban on using virgin HFCs with GWP ≥ 750 for servicing stationary refrigeration equipmentExisting chambers
2050HFC quotas reach zeroEveryone

Installed chambers can continue to operate: the regulation does not require them to be replaced, but it limits which gases can be used for recharging and repairs. Meanwhile, the quota system reduces the amount of HFCs available every year, so high-GWP gases are becoming increasingly scarce and expensive.


Already Own a Climatic Chamber?

  • Chambers using R404A or other gases with GWP ≥ 2,500: since 2025 they can no longer be recharged with virgin gas, and from 2030 not even with reclaimed gas. It is worth planning a refrigerant replacement in good time, for example with R449A.
  • Chambers using R23: if designed to operate below −50 °C they remain exempt from the servicing bans, but R23 will become increasingly expensive and hard to source.
  • After every repair: a second leak check is now mandatory between 24 hours and 30 days after the intervention.


Our Services

We carry out all operations required under the F-Gas Regulation, including:

  • Refrigerant leak detection and repair
  • Refrigerant recovery and charging
  • Refrigeration system leak testing
  • Refrigerant replacement
  • F-Gas register updates
  • Management of all mandatory documentation
  • Refrigerant recovery, recycling and disposal


Fully Compliant Operations

All activities are performed exclusively by F-Gas certified technicians, in full compliance with Regulation (EU) 2024/573.

Every intervention is documented according to current European regulations, ensuring complete traceability and full compliance for inspections and audits.

​

Ultra-Low Temperatures: The R23 Case

Below −50 °C there is currently no non-flammable refrigerant with a GWP below 150: CO₂ alone is not enough. For this reason the EU has granted a derogation until 31 December 2028 for chambers designed for applications below −50 °C, which must be labelled in accordance with Article 12(2) of the regulation.

For existing chambers using R23, a retrofit with lower-GWP refrigerants such as R472B (GWP 526) reduces the potential climate impact by more than 96% and protects you from the rising cost and limited availability of R23.


Service Benefits

Proper management of fluorinated refrigerants allows you to:

  • Maintain full regulatory compliance
  • Improve refrigeration system reliability
  • Reduce the risk of refrigerant leaks
  • Preserve the performance of your climatic chamber
  • Minimize environmental impact
  • Avoid non-compliance issues during inspections and audits

​

Support Throughout the Entire Equipment Life Cycle

Our F-Gas services can be integrated into every stage of your equipment's life cycle, including:

  • Installation and commissioning
  • Preventive maintenance
  • Corrective maintenance
  • Equipment overhaul
  • Refrigeration system retrofit
  • Refrigerant replacement
  • Equipment decommissioning


Frequently Asked Questions

Do I have to replace my climatic chamber by a certain date?
No. The regulation does not prohibit the use of existing chambers; it restricts which gases can be used for servicing.

Can I still buy a chamber that reaches −70 °C?
Yes. Chambers for applications below −50 °C can be placed on the market with refrigerants of GWP ≥ 150 until 31 December 2028, and they can continue to operate after that date.

Why not use only CO₂?
CO₂ (GWP 1) is an excellent solution down to about −50 °C. Below this threshold, cascade circuits with other refrigerants are required.

My chamber uses R404A: what should I do?
Contact us: we will assess whether to replace the refrigerant with a permitted one or whether replacing the chamber is the better option.


Request an F-Gas Assessment

Our specialists are available to verify your equipment's compliance and schedule all required F-Gas activities in accordance with current European regulations.


Contact us today to request a technical consultation or schedule an F-Gas service intervention.

This page is for information purposes only and does not constitute legal advice. The official text of Regulation (EU) 2024/573 prevails.

Request information

At your complete disposal for any information.

Please enter in the fields below, all the requested data. We will respond to your request as quickly as possible.